|Table of Contents|

Performance Analysis of a Hybrid Liquid Desiccant Air-ConditioningSystem with Sectional Utilization of Condensation Heat(PDF)

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

Issue:
2014年03期
Page:
33-
Research Field:
Publishing date:

Info

Title:
Performance Analysis of a Hybrid Liquid Desiccant Air-ConditioningSystem with Sectional Utilization of Condensation Heat
Author(s):
Zhang Fan1Wu Wei12Zhang Tiantian1Su Pengfei1Wang Hong1Chen Jian1Li Na1Wei Lishen1
(1.School of Energy and Mechanical Engineering,Nanjing Normal University,Nanjing 210042,China)(2.Engineering Laboratory of Energy System Process Conversion and Emission ReductionTechnology of Jiangsu Province,Nanjing Normal University,Nanjing 210042,China)
Keywords:
temperature and humidity independent control air-conditioning systemliquid desiccantvapor compression refrigerationε-NTUperformance analysis
PACS:
TB657.2
DOI:
-
Abstract:
In this paper,the condensation heat of vapor compression refrigeration system and solar energy are used as auxiliary heat source in the solution regeneration process.A novel hybrid liquid desiccant air conditioning system is established with efficiently sectional utilization of condensation heat.The ε-NTU model is used to conduct the theoretical analysis of the system.The paper studies the effects of indoor sensible heat load ratio,outdoor air condition as well as fresh air ratio on the performance of the system,and compared the results with the conventional liquid desiccant air conditioning system which does not utilize condensation heat as auxiliary heat source.It is concluded that even if electrical energy is used to assist regenerating solution,the system’s performance is better than that of the conventional system without utilization of condensation heat.The promotion will be more especially when ta and RH are relatively little.

References:

[1] 江亿.我国建筑能耗趋势与节能重点[J].建设科技,2006(7):10-13,15.
Jiang Yi,The trend of building energy consumption and the focus of energy conservation in our country[J].Construction Science and Technology,2006(7):10-13,15.(in Chinese)
[2]刘晓华,江亿.温湿度独立控制空调系统[M].北京:中国建筑工业出版社,2006.
Liu Xiaohua,Jiang Yi.Temperature and Humidity Independent Control Air-conditioning System[M].Beijing:China Architecture & Building Press,2006.(in Chinese)
[3]Niu Xiaofeng,Xiao Fu,Ge Gaoming.Performance analysis of liquid desiccant based air-conditioning system under variable fresh air ratios[J].Energy and Buildings,2010,42(12):2 457-2 464.
[4]Zhang Li,Dang Chaobin,Hihara Eiji.Performance analysis of a no-frost hybrid air conditioning system with integrated liquid desiccant dehumidification[J].International Journal of Refrigeration 2010,33(1):116-124.
[5]Lof G O G.Cooling with solar energy[C]//Congress on Solar Energy.Tucson,USA,1955:171-189.
[6]Howell J R,Peterson J L.Preliminary performance evaluation of a hybrid vapor compression/liquid desiccant air conditioning system[C]//ASME Paper 86-WA/sol.9.Anaheim,California,1986.
[7]Yadav Y K.Vapour-compression and liquid-desiccant hybrid solar space conditioning system for energy conservation[J].Renewable Energy,1995,6(7):719-723.
[8]Khalil A.An experimental study on multi-purpose desiccant integrated vapor-compression air conditioning system[J].International Journal of Energy Research,2012,36(4):535-544.
[9]Kaushik S C,Singh M.Feasibility and design studies for heat recovery from a refrigeration system with a canopus heat exchanger[J].Heat RecovSyst CHP,1995,15(7):665-673.
[10]Adran A Kinsara,Moustafa M Elsayed,Omer M Al-Rabghi.Proposed energy efficient air conditioning system using liquid desiccant[J].Applied Thermal Engineering,1996,16(10):791-806.
[11]Conde M R.Properties of aqueous solutions of lithium and calcium chlorides:formulations for use in air conditioning equipment design[J].Int J Therm Sci,2004,43(4):367-382.
[12]薛殿华.空气调节[M].北京:清华大学出版社,1991:26.
Xue Dianhua.Air Conditioning[M].Beijing:Tsinghua University Press,1991:26.(in Chinese)
[13]Stevens D I.Analysis of Liquid-Desiccant Systems and Component Modeling[D].Madison:University of Wisconsin,1988.
[14]Niu Xiaofeng,Xiao Fu,Ma Zhenjun.Investigation on capacity matching in liquid desiccant and heat pump hybrid air-conditioning systems[J].International Journal of Refrigeration,2012,35(1):160-170.
[15]Zhang Li,Eiji Hihara,Michiyuki Saikawa.Combination of air-source heat pumps with liquid desiccant dehumidification of air[J].Energy Conversion and Management,2012,57:107-116.
[16]Daou K,Wang R Z,Xia Z Z.Desiccant cooling air conditioning:a review[J].Renewable and Sustainable Energy Reviews,2006,10(2):55-77.
[17]Zhang Tao,Liu Xiaohua,Jiang Yi.Performance optimization of heat pump driven liquid desiccant dehumidification systems[J].Energy and Buildings,2012,52:132-144.
[18]Dai Y J,Wang R Z,Zhang H F,et al.Use of liquid cooling to improve the performance of vapor compression air conditioning[J].Applied Thermal Engineering,2001,21(12):1 185-1 202.
[19]吴业正,朱瑞琪,曹小林,等.制冷原理及设备[M].西安:西安交通大学出版社,2010:223.
Wu Yezheng,Zhu Ruiqi,Cao Xiaolin,et al.Principle and Refrigeration Equipment[M].Xi’an:Xi’an Jiaotong University Press,2010:223.(in Chinese)
[20]Li Yutong,Lu Lin,Yang Hongxing.Energy and economic performance analysis of an open cycle solar desiccant dehumidification air-conditioning system for application in Hong Kong[J].Solar Energy,2010,84(12):2 085-2 095.
[21]She Xiaohui,Yin Yonggao,Zhang Xiaosong.Thermodynamic analysis of a novel energy-efficient refrigeration system subcooled by liquid desiccant dehumidification and evaporation[J].Energy Conversion and Management,2014,78:286-296.

Memo