|Table of Contents|

Experimental Research on Heating Performance of Air SourceHeat Pump Double-End System in Winter(PDF)

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

Issue:
2020年04期
Page:
10-15
Research Field:
动力工程及工程热物理
Publishing date:

Info

Title:
Experimental Research on Heating Performance of Air SourceHeat Pump Double-End System in Winter
Author(s):
Dai Chunxiang1Xia Yi1Han Wei2Zhu Yixiu1
(1.School of Energy and Mechanical Engineering,Nanjing Normal University,Nanjing 210023,China)(2.Yangzhou Yihe Investment Development Co.,Ltd.,Yangzhou 225000,China)
Keywords:
fan coilground radiant heatingdefrostheating performanceair source heat pump
PACS:
TK-9
DOI:
10.3969/j.issn.1672-1292.2020.04.002
Abstract:
The paper conducts an air source heat pump double terminal practical application,tests the supply air temperature,ground temperature,indoor air temperature,main engine supply and return water temperature and supply and return of rooms with different floor decoration materials during winter heating at the fan coil and ground radiation air conditioner terminals water temperature and ground temperature,and then gets the temperature increase speed and indoor vertical temperature distribution of the two air conditioners. The results of the study show that:the former’s supply air temperature rises at a rate of 11.2 times that of the latter’s questioning rate,and under the two types of air-conditioning terminal heating,the former’s indoor air temperature at 1m rises at 3.73 times that of the floor heating terminal. It can reach a comfortable indoor temperature faster. Although the floor heating radiation slows the indoor heating speed,the uniformity of the vertical temperature distribution in the room is better than that of the fan coil.The defrosting of the main engine outdoor unit has a greater impact on the air supply temperature at the end of the fan coil. The end of the radiant floor,because the concrete layer of the ground has heat storage properties,has little effect on the surface temperature of the radiant floor and the temperature of the room. When the floor heating end is heated,the heating rate of the marble floor is 1.67 times that of the wooden floor,so the marble floor can reach a comfortable temperature faster.

References:

[1] 傅允准,蔡颖玲,陈帅,等. 毛细管地板辐射采暖特性试验研究[J]. 流体机械,2009,37(8):54-57.
[2]高智杰. 夏热冬冷地区不同供暖末端的供热特性及调控规律研究[D]. 西安:西安建筑科技大学,2013.
[3]唐海达,张涛,刘晓华. 长江流域住宅中混凝土辐射地板与风机盘管供暖性能实测[J]. 暖通空调,2017,47(11):97-103.
[4]袁旭东,贾磊,宋有强. 送风+辐射组合末端供暖动态特性研究[J]. 流体机械,2018,46(10):68-72.
[5]DANIEL R,LARS W,MATTIAS V,et al. CFD simulation and evaluation of different heating systems installed in low energy building located in sub-arctic climate[J]. Building and Environment,2015,89:160-169.
[6]HASAN K,MüSLüM A,MURAT S. A numerical investigation of fluid flow and heat transfer inside a room for floor heating and wall heating systems[J]. Energy and Buildings,2013,67:471-478.
[7]赵丽博. 辐射与通风混合供暖系统室内传热及舒适性研究[D]. 长沙:中南大学,2014.
[8]潘雷刚,徐昭炜,杨强,等. 户式空气源热泵供暖系统不同末端形式分析[J]. 暖通空调,2018,48(2):40-43.
[9]战乃岩,沈翔欧,赵艳萍. 不同供热形式末端性能研究[J]. 节能,2019,38(2):65-68.
[10]STANISLAVS G,ANDRIS J. Experimental research of thermal comfort conditions in small test buildings with different types of heating[J]. Energy Procedia,2015,78:2929-2934.
[11]曾璟,李念平,成剑林,等. 蓄能型空气源热泵地板辐射供暖系统的试验研究[J]. 建筑科学,2016,32(6):33-38.
[12]ANTONIO A M,JOSE M C L,FRANCISCO F H,et al. A comparison of heating terminal units:fan-coil versus radiant floor and the combination of both[J]. Energy and Buildings,2017,138:621-629.
[13]韩伟. 空气源热泵双末端系统应用研究[D]. 南京:南京师范大学,2019.
[14]中国建筑科学研究院. 辐射供暖供冷技术规程:JCJ142—2012[S]. 北京:行业标准-建筑工业,2012.
[15]中国标准化与信息分类编码研究所. 中等热环境PMV和PPD指数的测定及热舒适条件的规定:GB/T 18049—2000[S]. 北京:国家质量技术监督局,2000.
[16]王忠华,徐颖,刘晓燕,等. 不同地面覆盖层材料对低温热水地板辐射采暖系统的影响[C]//全国暖通空调制冷2010年学术年会. 杭州:中国制冷学会,2011:629-632.
[17]郭晓磊. 低温地板辐射采暖系统特点及木地板在其中的应用[J]. 中国人造板,2007,7:16-19

Memo

Memo:
-
Last Update: 2020-12-15