[1]姜忠磊,赵孝保,王若琳,等.进口空气状态参数对带热管回热制冷除湿系统性能的影响[J].南京师范大学学报(工程技术版),2014,14(02):034.
 Jiang Zhonglei,Zhao Xiaobao,Wang Ruolin,et al.Effects of Inlet Air State Parameters on Performance of Cooling Dehumidification System with Heat Tube Air Regenerator[J].Journal of Nanjing Normal University(Engineering and Technology),2014,14(02):034.
点击复制

进口空气状态参数对带热管回热制冷除湿系统性能的影响
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
14卷
期数:
2014年02期
页码:
034
栏目:
出版日期:
2014-06-30

文章信息/Info

Title:
Effects of Inlet Air State Parameters on Performance of Cooling Dehumidification System with Heat Tube Air Regenerator
作者:
姜忠磊赵孝保王若琳张敏王丽丽
南京师范大学能源与机械工程学院,江苏 南京 210042
Author(s):
Jiang ZhongleiZhao XiaobaoWang RuolinZhang MinWang Lili
School of Energy and Mechanical Engineering,Nanjing Normal University,Nanjing 210042,China
关键词:
热管除湿充液率
Keywords:
heat pipedehumidificationfilling rate
分类号:
TK172.4
文献标志码:
A
摘要:
本文进行了热管除湿系统的除湿性能实验研究,控制入口空气状态即空气干球温度、相对湿度和空气流量3个关键因素下进行除湿量测试,得到了热管除湿机单位功率除湿量随进口空气干球温度、相对湿度增加而增加,随着空气流量的增加,单位功率除湿量有最大值的试验结果.实验研究了热管充液率为0%、15%和30%工况下的热管除湿性能,发现热管充液率为0%、15%时的除湿量比充液率为30%时高36%~42%.
Abstract:
In this paper,the dehumidification performance of heat pipe exchanger is studied experimentally.Three key parameters of the inlet air state,namely,drybulb temperature,relative humidity and air flow rate are controlled in the experiment,respectively.The result shows that dehumidification capacity for Heat Tube Air Regenerator increases with the increased inlet drybulb temperature and relative humidity.The dehumidification capacity has a maximum value with the increase of air flow rate.The dehumidification performances of heat pipe with filling factor of 15% and 30% are analyzed in the experiment.The dehumidification capacity of heat pipe with filling factor of 15% is 36%~42% higher than that with filling factor of 30%.

参考文献/References:

[1]朱培根,王建勋,朱志平,等.热管在调温除湿机中的应用研究[J].暖通空调,2006,36(2):56-59.
Zhu Peigen,Wang Jianxun,Zhu Zhiping,et al.Application of heat pipe technology to temperature adjustment dehumidifiers[J].Heating Ventilating and Air Conditioning,2006,36(2):56-59.(in Chinese)
[2]朱志平,刘宇峰.一种新型除湿机的运用[J].流体机械,2002(20):251-254. Zhu Zhiping,Liu Yufeng.The use of a new type of dehumidifier[J].Fluid Machinery,2002(20):251-254.(in Chinese)
[3]Hill J M,Jeter S M.The use of heat pipe heat exchangers for enhanced dehumidification[C]//Proceedings of the ASHRAE Winter Meeting.New Orleans:ASHRAE Transactions,1994,100(1):91-102.
[4]Yau Y H.Application of a heat pipe heat exchanger to dehumidification enhancement in a HVAC system for tropical climates—a baseline performance characteristics study[J].International Journal of Thermal Sciences,2007,46(2):164-171.
[5]Yau Y H.Experimental thermal performance study of an inclined heat pipe heat exchanger operating in high humid tropical HVAC systems[J].International Journal of Refrigeration,2007,30(7):1 143-1 152.
[6]Yau Y H,Ahmadzadehtalatapeh M.A review on the application of horizontal heat pipe heat exchangers in air conditioning systems in the tropics[J].Applied Thermal Engineering,2010,30(2):77-84.
[7]Jouhara H,Merchant H.Experimental investigation of a thermosyphon based heat exchanger used in energy efficient air handling units[J].Energy,2012,39(1):82-89.

备注/Memo

备注/Memo:
收稿日期:2014-05-06.
基金项目:江苏省能源系统过程转化与减排技术工程实验室开放课题.
通讯联系人:赵孝保,博士,教授,研究方向:多孔介质内汽液两相流动、传热与传质以及热管技术应用.E-mail:zhao@njnu.edu.cn
更新日期/Last Update: 2014-06-30