[1]王子介.辐射采暖住宅建筑能耗与室内作用温度[J].南京师范大学学报(工程技术版),2002,02(02):078-83.
 Wang Zijie.Energy Consumption and Operating Temperature of Residential Building by Using Radiant Heating[J].Journal of Nanjing Normal University(Engineering and Technology),2002,02(02):078-83.
点击复制

辐射采暖住宅建筑能耗与室内作用温度
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
02卷
期数:
2002年02期
页码:
078-83
栏目:
出版日期:
2002-06-30

文章信息/Info

Title:
Energy Consumption and Operating Temperature of Residential Building by Using Radiant Heating
作者:
王子介
南京师范大学动力工程学院, 210042, 南京
Author(s):
Wang Zijie
College of Power Engineering,Nanjing Normal Hmversity, 210042, Nanjing, PRC
关键词:
辐射供暖 居住建筑 作用温度 建筑能耗 节能
Keywords:
r adiant heat ing residential building oper ating temperatur e building ener gy consumption energ y efficiency
分类号:
TU111.19
摘要:
对南京地区冬季采用地板辐射采暖的住宅进行了房间空气温度、围护结构表面温度、热源设备能耗的实测 ,在此基础上计算了室内平均辐射温度 (MRT)和作用温度 (OperationTemperature) ,并对外墙比例不同的房间的作用温度进行了对比 .研究结果证明 ,由于现有 2 40砖墙的住宅建筑围护结构保温性能较差 ,两面外墙较之一面外墙的房间 ,作用温度可相差 1℃以上 .对于所介绍的采暖系统形式 ,采暖期 (以 90d计 )每m2 建筑面积电耗 ,根据运行模式和室内设计温度的不同 ,为7.3kWh至 5 2kWh .
Abstract:
The air temperatur e, inner surface temperature and heating equipment energy consumptio n in w inter season were measur ed for an apartment equipped with radiant heating system. Based on the measur ed results, the average radiant temperature and operating temperature of different rooms with different outside walls w ere calculated and compared. The results show t hat the oper at ing temperature of rooms w ith tw o sides of outside w alls is more than 1℃ higher than that with one side of outside wall. The range of the energy consumptions of the heating system varies from 7. 3 kWh/ m2 to 52 kWh/ m2 for a heating season, depending on the equipment oper ating models and room design temperatures.

参考文献/References:

[ 1] 王子介. 地板供暖及其发展动向[ J] . 暖通空调, 1999, 6: 35~ 38.
[ 2] 王子介. 地板辐射供冷及地热空气源热泵可行性研究分析[ C] . 全国热泵和空调技术交流会论文集, 2001. 10: 258~ 265.
[ 3] 张建忠, 龚延风. 空气源热泵冷热水机组在南京的应用[ J] . 现代空调, 2001, 3: 141~ 156.
[ 4] B W Olesen, E Michel. Heat Ex change Co efficient Between Floor Surface and Space by Floor Cooling- Theory or a Questionof Definition[ J] . ASHRAE Transactions: Symposia, DA- 00- 8- 2: 684~ 694.
[ 5] B W Olsen. Possibilities and Limitat ions of Radiant Floor Cooling [ J] . ASHRAE Transactions 1997( 103) , 1: 42~ 48.
[ 6] 1999 ASHRAE Applications Handbook, Chapter 52[ Z] .

相似文献/References:

[1]王子介.地板辐射供暖系统能耗计算[J].南京师范大学学报(工程技术版),2006,06(01):001.
 WANG Zijie.An Energy Analysis Method for Radiant Floor Heating System[J].Journal of Nanjing Normal University(Engineering and Technology),2006,06(02):001.
[2]王子介,夏学鹰.地板辐射供冷/暖的简化动态模型及其应用[J].南京师范大学学报(工程技术版),2004,04(01):001.
 Wang Zijie,Xia Xueying.One-Dimensional Dynamic Models for Radiant Floor Heating/Cooling[J].Journal of Nanjing Normal University(Engineering and Technology),2004,04(02):001.

备注/Memo

备注/Memo:
基金项目: 南京师范大学高层次人才科研项目( 2001DLYXGQB901) .
作者简介: 王子介, 1948- , 南京师范大学动力工程学院教授, 从事建筑节能与暖通空调新技术方面的研究与教学.
更新日期/Last Update: 2013-04-29