[1]牛宝联,宋倩倩,夏学鹰,等.应用于辐射供冷系统的双级热泵复合除湿空调系统及能耗分析[J].南京师范大学学报(工程技术版),2009,09(03):037-41.
 Niu Baolian,Song Qianqian,Xia Xueying,et al.Energy-saving Refrigeration and Dehumidification Unit on Radiant Cooling and its Energy-Consumption Analysis[J].Journal of Nanjing Normal University(Engineering and Technology),2009,09(03):037-41.
点击复制

应用于辐射供冷系统的双级热泵复合除湿空调系统及能耗分析
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
09卷
期数:
2009年03期
页码:
037-41
栏目:
出版日期:
2009-09-30

文章信息/Info

Title:
Energy-saving Refrigeration and Dehumidification Unit on Radiant Cooling and its Energy-Consumption Analysis
作者:
牛宝联;宋倩倩;夏学鹰;吴薇;
南京师范大学动力工程学院, 江苏南京210042
Author(s):
Niu BaolianSong QianqianXia XueyingWu Wei
School of Power Engineering,Nanjing Normal University,Nanjing 210042,China
关键词:
辐射供冷 除湿机组 能耗分析
Keywords:
radian t coo ling duhum id ify ing un it energy consum ption analysis
分类号:
TU831
摘要:
为减少辐射供冷系统热湿处理机组的能耗,提出采用两级热泵与除湿单元联用的系统形式.低温热泵子系统提供辐射供冷所需的冷负荷,高温热泵子系统则根据设计的系统形式大小不同,可长期运行,也可与蓄热水箱或者太阳能联用3种方式.并对3种方式下的液体除湿、固体除湿与传统的冷却除湿,液体除湿+冷水机组和固体除湿+冷水机组的形式进行能耗分析对比,结果表明3种方式下的液体除湿和固体除湿系统都较节能,且以3种改进方式与液体除湿联用的系统最为节能,与冷却除湿相比,能源消耗可以减少48%.
Abstract:
In order to save ene rgy o f heating and dehum idify ing unit in radiant cooling sy stem, it is proposed tha t the comb ined use of two-stage hea t pum p and dehum idify ing unit. Low- temperature- stage hea t pum p is used to supply coo-l ing load of rad iant cooling system, and h igh-temperature-stage hea t pum p is designed in three shapes. One is low load system that is only to dehum id ify w hen the room is need to, the o ther tw o are not on ly dehum idify ing but also are comb ined w ith heat sto rage water tank or so lar energy. And the energy consumption ana lys is is done on the new system style o f liquid dehum idify ing, so lid dehunidify ing, and coo ling de fum id ify ing, in contrast to liqu id dehum id ify ing+ w ater ch i-l ler, and so lid de fum id ify ing+ w ater chiller. The results show that liqu id and so lid dehum id ify ing arem o re energy- saving, and the th ree new system + liqu id dehum id ify ing is the m ost energy-sav ing and the energy consum ption is reduced by 48% w hen com pared w ith coo ling dehum idify ing.

参考文献/References:

[ 1] Jae-W eon Jeong, StanleyA M umm a. Ce iling rad iant coo ling panel capacity enhanced bym ixed convection in m echan ica lly ventilated
spaces[ J] . App lied The rma l Eng ineer ing, 2003, 23: 2 293-2 306.
[ 2] 丁云飞, 丁静, 杨晓西. 基于太阳能再生的转轮除湿独立新风系统[ J] . 流体机械, 2006, 34( 8): 63-66.
Ding Yunfe ,i D ing Jing, Yang X iaox.i Ded icated outdoo r a ir system s by rotary whee l rem ov ing mo isture load based on so lar ene
rgy regeneration[ J]. FluidM achinery, 2006, 34( 8): 63-66. ( in Ch inese)
[ 3] 丁云飞, 丁静, 王卓越, 等. 除湿转轮处理冷却顶板空调系统的湿负荷[ J]. 华南理工大学学报: 自然科学版, 2004, 32
( 3): 10-14.
Ding Yunfe ,i D ing Jing,W ang Zhuoyue, e t a .l Rem ov ing of m o isture load in coo ling ceiling air-condition ing system by rotary
dehum id ifier[ J]. Journal of Sou th Ch ina University o f Techno logy: Natural Sc ience Edition, 2004, 32( 3): 10-14. ( in Ch-i
nese)
[ 4] 孙健, 施明恒. 太阳能液体除湿空调系统性能参数的研究[ J]. 流体机械, 2007, 35( 7): 61-66.
Sun Jian, ShiM ingheng. Study on co efficien t of perform ance o f solar liqu id desiccant a ir- cond ition ing system [ J]. F lu idM ach
inery, 2007, 35( 7): 61-66. ( in Ch inese)
[ 5] 施明恒, 杜斌, 赵云. 太阳能液体除湿空调系统再生和蓄能特性的研究[ J]. 太阳能学报, 2006, 27( 1): 49-53.
ShiM ingheng, Du B in, Zhao Yun. Investiga tion on the regeneration and ene rgy storge cha racte ristic of a so la r liqu id desiccant
air-conditioner[ J]. A cta Energ iae So la ris Sinica, 2006, 27( 1): 49-53. ( in Chinese)
[ 6] 施泰姆勒F. 湿度控制与冷却顶棚[ J] . 戴茹, 曹叔维, 译. 暖通空调, 1998, 28( 2): 1-4.
Ste im le F. M o isture contro l and coo ling ceilings[ J]. Da i Ru, Cao Shuwe ,i Translation. HV&AC, 1998, 28( 2) : 1-4. ( in
Chinese)

备注/Memo

备注/Memo:
基金项目: 住房和城乡建设部( 2008-k1-25 )资助项目.
通讯联系人: 牛宝联, 博士, 讲师, 研究方向: 制冷与热泵系统优化. E-m ail:lniubaolian@ 163. com
更新日期/Last Update: 2013-04-23