[1]罗 朗,余跃进,郑丽鹏,等.添加隔热板对竖直U型地埋管换热器热短路的影响[J].南京师范大学学报(工程技术版),2016,16(01):066.
 Luo Lang,Yu Yuejin,Zheng Lipeng,et al.Influence of Adding the Insulation Board on Hot Short Circuit ofthe Vertical U-Tube Ground Heat Exchanger[J].Journal of Nanjing Normal University(Engineering and Technology),2016,16(01):066.
点击复制

添加隔热板对竖直U型地埋管换热器热短路的影响
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
16卷
期数:
2016年01期
页码:
066
栏目:
能源工程
出版日期:
2016-03-31

文章信息/Info

Title:
Influence of Adding the Insulation Board on Hot Short Circuit ofthe Vertical U-Tube Ground Heat Exchanger
作者:
罗 朗余跃进郑丽鹏夏 雯
南京师范大学能源与机械工程学院,江苏 南京 210042
Author(s):
Luo LangYu YuejinZheng LipengXia Wen
School of Energy and Mechanical Engineering,Nanjing Normal University,Nanjing 210042,China
关键词:
U型地埋管隔热板数值模拟换热性能
Keywords:
U-type buried tubeinsulation boardnumerical simulationheat exchange performance
分类号:
TK01+8
文献标志码:
A
摘要:
采用FLUENT模拟软件,建立起U型地埋管换热器三维传热模型.分别模拟了有、无添加隔热板时的工况,对热短路进行数值模拟,分析了对地埋管换热器性能的影响.通过对比两种工况下的温度云图和出口温度监测图,证明了两支管间热短路现象严重,而且添加隔热板后,进出口温差变大可达3.94 ℃,可使单位井深换热量提升6.13%.
Abstract:
The paper simulates with FLUENT software to build three -dimensional heat transfer model of U-tube buried tube heat exchanger. When adding insulation panels are simulated with and without conditions,to simulate the thermal circuit,the influence of the performance of ground heat exchanger is analyzed. By comparing the two kinds of working conditions of temperature and outlet temperature monitoring diagram,simulation proves that the hot short circuit phenomenon is serious between the two branch pipe,and after adding insulation board,the import and export temperature difference can reach 3.94 ℃,and the unit well depth in heat can be made to improve 6.13%.

参考文献/References:

[1] 杨卫国,王京. 地源热泵系统热短路分析[J]. 建筑节能,2008,36(2):12-14.
YANG W G,WANG J. Thermal circuit analysis of ground source heat pump system[J]. Building energy-saving,2008,36(2):12-14.(in Chinese)
[2] 姚奇志,刘秋新,石文,等. 地源热泵地埋管热短路问题的研究[J]. 制冷与空调(四川),2012(6):536-540.
YAO Q Z,LIU Q X,SHI W,et al. Ground heat exchanger of ground source heat pump heat short-circuit problem[J]. Refrigeration and air conditioning(Sichuan),2012(6):536-540.(in Chinese)
[3] 吴金星,郭桂宏,李俊超,等. U型埋管换热器管间热短路性能数值分析[J]. 制冷与空调(四川),2014,(1):16-21.
WU J X,GUO G H,LI J C,et al. U-type buried tube heat exchanger tube numerical analysis of short-circuit characteristics[J]. Refrigeration and air conditioning(Sichuan),2014(1):16-21.(in Chinese)
[4] CENK Y,JEFFREY D S. Field validation of a short time step model for vertical ground-loop heat exchangers/Discussion[J]. Atlanta:a SHRAE transactions,2001(9):617.
[5] 杨正武,秦萍,刘宇,等. U型地埋管换热器热短路特性研究[J]. 制冷与空调(四川),2009,23(3):59-63.
YANG Z W,QING P,LIU Y. U-tube buried tube heat exchanger heat short-circuit characteristics[J]. Refrigeration and air conditioning(Sichuan),2009,23(3):59-63.(in Chinese)
[6] 沈国民,张虹. 竖直U型埋管地热换热器热短路现象的影响参数分析[J]. 太阳能学报,2007,28(6):604-607.
SHEN G M,ZHANG H. Vertical U-tube geothermal heat exchangers heat effect of a short circuit parameter analysis[J]. Journal of solar energy,2007,28(6):604-607.(in Chinese)

备注/Memo

备注/Memo:
收稿日期:2015-11-19. 
通讯联系人:余跃进,教授,研究方向:空调系统优化、地源热泵技术、建筑物通风技术. E-mail:dlkj@njnu.edu.cn