[1]王佳敏,夏学鹰,李 栋,等.热虹吸管换热器应用于除湿系统的节能性分析[J].南京师范大学学报(工程技术版),2021,21(04):001-7.[doi:10.3969/j.issn.1672-1292.2021.04.001]
 Wang Jiamin,Xia Xueying,Li Dong,et al.Energy-saving Analysis of Thermosiphon Heat ExchangerUsed in Dehumidification System[J].Journal of Nanjing Normal University(Engineering and Technology),2021,21(04):001-7.[doi:10.3969/j.issn.1672-1292.2021.04.001]
点击复制

热虹吸管换热器应用于除湿系统的节能性分析
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
21卷
期数:
2021年04期
页码:
001-7
栏目:
动力工程及工程热物理
出版日期:
2021-12-15

文章信息/Info

Title:
Energy-saving Analysis of Thermosiphon Heat ExchangerUsed in Dehumidification System
文章编号:
1672-1292(2021)04-0001-07
作者:
王佳敏1夏学鹰1李 栋1赵孝保1苏晓翔2
(1.南京师范大学能源与机械工程学院,江苏 南京 210023)(2.联发智能科技股份有限公司,福建 厦门 361000)
Author(s):
Wang Jiamin1Xia Xueying1Li Dong1Zhao Xiaobao1Su Xiaoxiang2
(1.School of Energy and Mechanical Engineering,Nanjing Normal University,Nanjing 210023,China)(2.Lianfa Intelligent Technology Co.,Ltd.,Xiamen 361000,China)
关键词:
热虹吸管换热器除湿量除湿能耗比析湿系数能量利用率
Keywords:
thermosiphon heat exchangerdehumidification amountspecific power consumptionmoisture separation coefficientenergy utilization
分类号:
TU834.9
DOI:
10.3969/j.issn.1672-1292.2021.04.001
文献标志码:
A
摘要:
对加装热虹吸管换热器的除湿机与普通除湿机的性能进行了对比试验研究,并以环境温度27 ℃,空气相对湿度60%工况为例,对比分析了系统除湿性能及节能性. 实验结果表明,不同雷诺数条件下,与普通除湿机相比,加装热虹吸管换热器的除湿机除湿量可提高至少24%,除湿能耗比降低至少20%,析湿系数提高30%以上,能量利用率提高至少4.3倍. 结果表明,加装热虹吸管换热器的除湿机具有更高的除湿性能且节能效果显著. 然后,进一步分析了加装热虹吸管换热器的除湿系统除湿量、雷诺数与能量利用率之间的关系. 最后,拟合得到了三者的试验关联式.
Abstract:
A comparative experimental study on the performance of dehumidifier equipped with thermosiphon heat exchanger and regular dehumidifier is conducted and a comparative analysis is carried out concerning the dehumidifying performance and energy saving property under the operating condition in which the ambient temperature equals to 27 ℃ and the air relative humidity is 60%. The experimental results indicate that under different Reynolds number conditions,the dehumidification amount of dehumidifier equipped with thermosiphon heat exchanger increases at least 24% and the specific power consumption decreases at least 20% compared with the regular dehumidifier. Besides,the moisture separation coefficient increases by more than 30% and the energy utilization is enhanced by at least 4.3 times. The result show that the dehumidifier equipped with thermosiphon heat exchanger has higher dehumidification performance and remarkable energy-saving effect. In addition,the relation among the dehumidification amount,Reynolds number and energy utilization is further analyzed and the correlation of the three factors is obtained.

参考文献/References:

[1] 田向宁,杨毅,丁德,等. 空气冷却除湿过程的理论研究[J]. 暖通空调,2014(1):121-124.
[2]陈晓阳,江亿,李震,等. 湿度独立控制空调系统的工程实践[J]. 暖通空调,2004,34(11):103-109.
[3]解鸣,茆春俊,吕雯,等. 基于热管传热的除湿溶液真空再生过程实验研究[J]. 制冷学报,2019,40(6):103-110.
[4]陈剑波,李美玲,韩星,等. 辐射空调用节能新风控温除湿机除湿性能实验研究[J]. 制冷学报,2015,36(3):79-91.
[5]HILL J M,JETER S M. Use of heat pipe heat exchangers for enhanced dehumidification[J]. Ashrae Transactions,1994,100(1):91-102.
[6]YAU Y H. Application of a heat pipe heat exchanger to dehumidification enhancement in a HVAC system for tropical climates—a baseline performance characteristics study[J]. International Journal of Thermal Sciences,2007,46(2):164-171.
[7]YAU Y H. Experimental thermal performance study of an inclined heat pipe heat exchanger operating in high humid tropical HVAC systems[J]. International Journal of Refrigeration,2007,30(7):1143-1152.
[8]YAU Y H,AHMADZADEHTALATAPEH M. A review on the application of horizontal heat pipe heat exchangers in air conditioning systems in the tropics[J]. Applied Thermal Engineering,2010,30(2):77-84.
[9]JOUHARA H,MERCHANT H. Experimental investigation of a thermosyphon based heat exchanger used in energy efficient air handling units[J]. Energy,2012,39(1):82-89.
[10]朱培根,王建勋,朱志平,等. 热管在调温除湿机中的应用研究[J]. 暖通空调,2006,36(2):56-59.
[11]杨光. 整体式热管的设计开发与全热回收器的实验研究[D]. 长沙:湖南大学,2007.
[12]赵荣义. 空气调节[M]. 4版. 北京:中国建筑工业出版社,2008.

备注/Memo

备注/Memo:
收稿日期:2021-01-18.
通讯作者:夏学鹰,博士,副教授,研究方向:辐射冷暖理论与实践. E-mail:sdxxynsd@126.com