[1]刘寒春,周建明,刘守城,等.特快速暂态过电压信号下的屏蔽线端口串扰电压分析[J].南京师范大学学报(工程技术版),2021,21(04):008-12.[doi:10.3969/j.issn.1672-1292.2021.04.002]
 Liu Hanchun,Zhou Jianming,Liu Shoucheng,et al.Transient Analysis of Shielded Cable Crosstalk Under VFTO Signal[J].Journal of Nanjing Normal University(Engineering and Technology),2021,21(04):008-12.[doi:10.3969/j.issn.1672-1292.2021.04.002]
点击复制

特快速暂态过电压信号下的屏蔽线端口串扰电压分析
分享到:

南京师范大学学报(工程技术版)[ISSN:1006-6977/CN:61-1281/TN]

卷:
21卷
期数:
2021年04期
页码:
008-12
栏目:
电气工程
出版日期:
2021-12-15

文章信息/Info

Title:
Transient Analysis of Shielded Cable Crosstalk Under VFTO Signal
文章编号:
1672-1292(2021)04-0008-05
作者:
刘寒春1周建明23刘守城23赵 阳23
(1.江苏省医疗器械检验所,江苏 南京 210019)(2.南京师范大学南瑞电气与自动化学院,江苏 南京 210023)(3.南京师范大学江苏省电气装备与电磁兼容工程实验室,江苏 南京 210023)
Author(s):
Liu Hanchun1Zhou Jianming23Liu Shoucheng23Zhao Yang23
(1.Jiangsu Medical Device Inspection Institute,Nanjing 210019,China)(2.School of NARI Electrical and Automation,Nanjing Normal University,Nanjing 210023,China)(3.Jiangsu Electrical Equipment EMC Engineering Laboratory,Nanjing Normal University,Nanjing 210023,China)
关键词:
特快速暂态过电压串扰屏蔽线时域有限差分法
Keywords:
very fast transient over-voltagecrosstalkshielded cablefinite difference time domain
分类号:
TM72
DOI:
10.3969/j.issn.1672-1292.2021.04.002
文献标志码:
A
摘要:
研究气体绝缘变电站(gas insulated subsation,GIS)中隔离开关进行分合闸操作时,其绝缘气体被击穿所产生的特快速暂态过电压(very fast transient over-voltage,VFTO)在线缆中的传输特性. 将传输线系统分为内、外回路,分别运用域有限差分法对电报方程进行求解,得到传输线的端口暂态响应. 计算结果与CST CABLE STUDIO仿真结果高度吻合,表明所提模型与计算方法的有效性,该方法的提出对于一、二次侧传输线缆的串扰、衰减特性分析具有重要意义.
Abstract:
This article aims to study the transmission characteristics of the very fast transient over-voltage(VFTO)generated by the breakdown of the insulating gas when the isolating switch in a gas insulated substation(GIS)is opened and closed. In this paper,the transmission line system is divided into inner and outer loops,and the telegraph equation is solved by the finite difference method respectively,and the transient response of the transmission line port is obtained. The calculation results are highly consistent with the CST CABLE STUDIO simulation results,which proves the effectiveness of the proposed model and calculation method. The proposed method is of great significance to the analysis of the crosstalk and attenuation characteristics of the primary and secondary transmission cables.

参考文献/References:

[1] ZHAN H,DUAN S,LI C,et al. A novel arc model for very fast transient overvoltage simulation in a 252-kV gas-insulated switchgear[J]. IEEE Transactions on Plasma Science,2014,42(10):3423-3429.
[2]YUE G C,LIU W D,CHEN W J,et al. Development of full frequency bandwidth measurement of VFTO in UHV GIS[J]. IEEE Transactions on Power Delivery,2013,28(4):2550-2557.
[3]MA G M,LI C R,ZHOU H Y,et al. Time and frequency characteristics of very fast transient overvoltage in ultra high voltage substation[J]. IEEE Transactions on Dielectrics and Electrical Insulation,2017,24(4):2459-2468.
[4]GUAN Y,YUE G,CHEN W,et al. Experimental research on suppressing VFTO in GIS by magnetic rings[J]. IEEE Transactions on Power Delivery,2013,28(4):2558-2565.
[5]PAUL C R. Transmission-line MNodeling of shielded wires for crosstalk prediction[J]. IEEE Transactions on Electromagnetic Compatibility,1981,23(4):345-351.
[6]XU M,WANG Y,LI X,et al. Analysis of the influence of the structural parameters of aircraft braided-shield cable on shielding effectiveness[J]. IEEE Transactions on Electromagnetic Compatibility,2020,62(4):1028-1036.
[7]LI A D,LIU Q,YANG J Y,et al. Crosstalk analysis between power lines and signal lines based on the finite difference-time domain method[C]//2019 IEEE 8th International Conference on Advanced Power System Automation and Protection(APAP). Xi’an,China,2019:638-641.
[8]唐丽娟,叶志红,陈伶璐,等. 单导体传输线与屏蔽电缆串扰问题的研究[J]. 科学技术与工程,2013,13(36):10913-10916.
[9]YU T,THOMAS D W P,CHRISTOPOULOS C. Time-domain simulation of crosstalk between coaxial cables[C]//2013 Asia-Pacific Symposium on Electromagnetic Compatibility(APEMC). Melbourne,Australia,2013:1-4.
[10]VANCE E F. Shielding effectiveness of braided-wire shields[J]. IEEE Transactions on Electromagnetic Compatibility,1975,17(2):71-77.
[11]TYNI M. The transfer impedance of coaxial cables with braided outer conductors[C]//Proceedings 3rd International Symposium Electromagnetic Compatibility. Wroclaw,Poland,1976.
[12]DEMOULIN B,DEGAUQUE P,CAUTERMAN M,et al. Shielding performance of triply shielded coaxial cables[J]. IEEE Transactions on Electromagnetic Compatibility,1980,22(3):173-180.
[13]康兵. GIS中特快速暂态过电压及其对电子式互感器影响的研究[D]. 武汉:武汉大学,2016.
[14]KLEY T. Optimized single-braided cable shields[J]. IEEE Transactions on Electromagnetic Compatibility,1993,35(1):57-63.
[15]BRANACˇíK L. Time-domain simulation of hybrid systems with nonuniform multiconductor transmission lines in Matlab[C]//2012 International Conference on Mathematical Methods in Electromagnetic Theory. Kyiv,Kraine. 2012:168-171.

相似文献/References:

[1]周建明,张海龙,赵 阳,等.基于天牛群-反馈神经网络的绞线串扰预估[J].南京师范大学学报(工程技术版),2022,22(02):023.[doi:10.3969/j.issn.1672-1292.2022.02.004]
 Zhou Jianming,Zhang Hailong,Zhao Yang,et al.Prediction of Twisted Wire Crosstalk Based on Beetle Swarm Optimization-Back Propagation Neural Network[J].Journal of Nanjing Normal University(Engineering and Technology),2022,22(04):023.[doi:10.3969/j.issn.1672-1292.2022.02.004]

备注/Memo

备注/Memo:
收稿日期:2021-07-19.
基金项目:江苏省社会发展重点项目(BE2019716)、电网环境保护国家重点实验室开发基金项目(GYW51202001558).
通讯作者:赵阳,博士,教授,研究方向:电磁兼容. E-mail:zhaoyang2@njnu.edu.cn